FXPRO

FXPRO is the heart of this new control units series and manages up to 5 analogue addressable loops with AS, Evolution or IE protocols with the ability to coordinate loops also simultaneously with different protocols. It is possible to add up to 3 FXUP modular units via RS485 to FXPRO in order to manage up to 20 loops.
FXPRO integrates a frontal control panel. The interface is very clear and any configuration, control, monitoring and command operations are very easy.
The connectivity and the possibility to create a control units net are additional key points of the FXPRO analogue-addressable fire detection control units. FXPRO is certified CPR 305/2011 (ex CPD 89/106/EEC) EN54-2 and EN54-4.
  • Number of detection loop Up to 5
    Number of loop address 254 (up 512 per control unit)
    Protocols

    AS with FX/EXP01 module

    Evolution with FXEXPEV

    IE with FXEXPIE module

    Zones number 120
    FXUP expansion Up to 3 FXUP additional
    Fault relay output 2 outputs
    Alarm relay output 1 programmable output
    Supervised alarm outputs 3 programmable outputs + 1 not programmable output
    DC24V output (LOAD) 1
    General LEDs indication Yes
    LCD display 4 x 20 character
    Control panel Built-in for management and programming
    Management levels 3 access levels with 10 associated user password from step 1 at 2 level and 10 installer password associated from step 2 to level 3
    Peripherals serial lines 1 for repeaters, synoptic and “intelligent” power supplies units management
    Extinguishing management Through external control unit
    Remote assistance With WINFIRE PRO software
    Management software With GLOBALPRO, GPROFIRE and WINFIRE PRO software
    Control units and PC network Up to 16
    Events storage 4000 events
    Devices storage Graphic display of the log devices
    Functions

    Management of input and output devices through logic events, system events, and patterns

    Definition of filters for special management of events memory and printing process;

    Weekly programmer with day/night function

    Date/time setup and daylight saving time switch

    Sensor control

    Delayed mode

    Sensitivity with thresholds that can be programmed for alarm, pre-alarm, and maintenance

    Loop devices self-learning with double-address identification

    Power supply units 4A @ DC24V: 1,5A buffer battery charge, 0,5A max to the LOAD terminal for auxiliary device powered
    Allocable batteries (not included) 2 x 26Ah/12V
    Power consumption (Absorption of any device linked to the relay outputs of panel and unit boards is not included)

    810 mA @ 230 VAC from mains.

    Unit boards: 280 mA @ 24 VDC at rest, 410 mA @ 24 VDC in alarm conditions (max 520 mA when the max number of contemporaneously lit LEDs is on).

    For each FXMASTERINT board: 12 mA @ 24 VDC.

    Absorption of FX/EXP01single loop boards: 31 mA @ 24 VDC (without detectors), 82 mA @ 24 VDC (with 254 detectors (using smoke detectors)

    Absorption of FXEXPEV single loop boards: 75 mA @ 24 VDC (without detectors), 150mA @ 24 VDC (with 254 detectors (using smoke detectors)

    Absorption of FXEXPIE single loop boards: 25 mA @ 24 VDC (without detectors), 165mA @ 24 VDC (with 254 detectors (using smoke detectors)

    Power supply 230 Vca
    Operating temperature -5 / +40°C, 93% U.R.
    Dimensions and weight W500 x H570 x D190 mm, 15,5Kg (with transformer)
    Protection class IP3X
    Certifications CPR 305/2011 certification  (ex CPD 89/106/EEC certification) EN54-2 and EN54-4
  • FXPRO

    1820.71 KB

    • FXPRO 2017

      Brochure delle centrali antincendio modulari FXPRO

    fxpro

    1818.67 KB

    • FXPRO 2017

      FXPRO modular analogue-addressable fire detection control units

  • Software Configuration

    Datasheet

    • Foglio tecnico
      Model
      23/05/2016
       
    • Datasheet
      Model
      23/05/2016
       

    Product Description

    • Descrizioni Capitolato
      Model
      23/05/2016
       
    • Product Description
      Model
      23/05/2016
       

    User Manual

    Quick Guide

    • Guida Rapida
      Model
      11/07/2017
       
    • Quick Guide
      Model
      29/06/2017
       

    Technical Manual

    • Manuale Tecnico
      Model
      11/07/2017
       
    • Technical Manual
      Model
      29/06/2017
       

    Programming Manual

    • Manuali di Programmazione
      Model
      11/07/2017
       
    • Development Manual
      Model
      11/07/2017
       

    CE - DoP

    • CE - DoP
      Model
      29/08/2017
       
    • CE - DoP
      Model
      11/08/2017
       

    Notified Body

    • Ente Notificato
      Model
      29/08/2017
       
    • Ente Notificato
      Model
      11/08/2017
       
  • User Manual

    Quick Guide

    • Guida Rapida
      Model
      23/05/2016
       
    • Quick Guide
      Model
      23/05/2016
       

    Technical Manual

    • Manuale Tecnico
      Model
      23/05/2016
       
    • Technical Manual
      Model
      23/05/2016
       

    Programming Manual

    • Manuali di Programmazione
      Model
      11/07/2017
       
    • Development Manual
      Model
      29/06/2017
       
    • Manuali di Programmazione
      Model
      23/05/2016
       
    • Programming Manual
      Model
      23/05/2016
       
    • CIFX00200100
      Centrale antincendio analogico indirizzata a 5 loop con interfaccia di comando
    • CIFX00200101
      5 Loop Analogue Addressable fire detection control panel with command interface - English version
    • CIFX00200104
      5 Loop Analogue Addressable fire detection control panel with command interface - German version
    • CIFX00200106
      5 Loop Analogue Addressable fire detection control panel with command interface - Spanish version
    • CIFX00200700
      Kit centrale antincendio analogico indirizzata a 5 loop con interfaccia di comando FXPRO con trasformatore TMFX
    • CIFX00200701
      Kit composed by 5Loop Analogue Addressable fire detection control panel with command interface FXPRO with TMFX transformer - EN Version
    • CIFX00200704
      Kit composed by 5Loop Analogue Addressable fire detection control panel with command interface FXPRO with TMFX transformer - DE version
    • CIFX00200706
      Kit composed by 5Loop Analogue Addressable fire detection control panel with command interface FXPRO with TMFX transformer - ES version

Active Products