Type |
Analogue-addressable panel |
|
Address/loop management |
250 overall addresses on 1 or 2 loops (using HL2LOOP board) or 500 overall addresses on 2 or 4 loops (using HL4LOOP board) |
|
Maximum current on each single loop |
1 A |
|
Panel network |
All the devices can be managed from all the panels |
|
Multimaster panel network |
Yes (via RS422 serial line with HLNET optional board) |
|
Manageable zones |
384 available zones |
|
Manageable I/O device groups |
512 available groups |
|
Manageable alarm device groups |
512 available groups |
|
Signal propagation |
propagation of all the events |
|
Maximum network expansion |
124 loops |
|
Protocol |
management of FYRA loop devices |
|
Management of HLPOWER units on the loop |
Yes, using HLPL optional board |
|
Programming connector |
USB |
|
Technological zone management |
Yes |
|
Delay mode 2 (according to italian M.D.) |
Yes |
|
System event log |
10.000 events |
|
Display |
240 x 64 pixel backlit LCD display |
|
External LED indicators |
Yes |
|
Programming |
Via software and local keypad |
|
Batteries |
2 × 12 Ah / 12 Vdc batteries |
|
Dimensions |
W 340 x H 370 x D 145 mm |
|
Main board current draw when idle |
60 mA |
|
Power supply unit supplied current |
2.3 A @ 28.5 Vdc |
|
Power supply |
AC230V with internal power supply unit |
|
Regulations |
certified CPR 305/2011 EN54-2 and EN 54-4 |